Double Insulated PVC Wire - CU/XLPE/PVC - 6181XY

Double Insulated PVC Wire - CU/XLPE/PVC - 6181XY

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 7889.
 

Technical Data

Voltage Rating : 1.5 mm2 to 630 mm2 - 600 / 1000V Temperature Range : -15 °C to 90°C Minimum Bending Radius
4.0 to 50 mm2 : 10 X Overall diameter. 70 & 630 mm2 : 12 X Overall diameter. Test Voltage : 2 kV 15 min.

Cable Construction

Conductor

Plain annealed copper conductor : 4 mm2 to 630 mm2 stranded class 2 complying with BS EN 60228, HD 383, IEC 60228
Insulation : GP8 conforming to BS 7655-1.3 ( XLPE ) Sheath : Type 9 specified in BS 7655-4.2 Insulation Colour : Natural
Sheath Colour : Black

Cable Design Parameters

 

Part Number

Nominal Cross Sectional Area (Sq. mm)

Nominal Insulation Thickness (mm)

Nominal sheath Thickness (mm)

Approx Overall Diameter  (mm)

 

Approx. Net Weight (kg/km)

011600100004

4

0.70

1.40

8.0

107

011600100006

6

0.70

1.40

8.5

132

011600100010

10

0.70

1.40

9.5

181

011600100016

16

0.70

1.40

10.5

247

011600100025

25

0.90

1.40

12.0

358

011600100035

35

0.90

1.40

13.0

466

011600100050

50

1.00

1.40

14.0

545

011600100070

70

1.10

1.40

16.0

765

011600100095

95

1.10

1.50

18.0

1022

011600100120

120

1.20

1.50

20.0

1267

011600100150

150

1.40

1.60

22.0

1556

011600100185

185

1.60

1.60

24.0

1928

011600100240

240

1.70

1.70

27.0

2501

011600100300

300

1.80

1.80

29.0

3108

011600100400

400

2.00

1.90

32.0

3923

011600100500

500

2.20

2.00

36.0

4999

011600100630

630

2.40

2.20

40.0

6414