Multi Core Fire Resistant Cable

Multi Core Fire Resistant Cable

Application

These cables are designed for installations in trunking and conduits where a fire situation may pose a major hazard. Circuit integrity is maintained and to achieve optimum performance such cables should be installed in metal conduits.

Eneral Characteristics

GTemperature Rating : -20°C to +90°C
Voltage Rating (Uo/U) : 450/750V

Minimum Bending Radius Fixed : 8 x overall diameter

Sheath color : Generally Black

Cable Construction

Conductors: Stranded plain annealed copper conductor to BS EN 60228, class 2.

Insulation: Mica (fire resistant) tape covered by an extruded layer of cross - XLPE, insulating compound Other insulation options  Thermoset LSZH (EI-5) insulating compound

Sheath: LSZH (LTS-1) Sheathing compound
Other sheath options  PVC FR-LSH

Properties

Acid Gas Emission : IEC 60754-1, BS EN 50267-2-1

Smoke Emission : IEC 61034, BS EN 50268

Flame Propagation : EN 60332-1, EN 60332-3, BS EN 50265, BS EN 5026

Nominal area Sq.mm

Current Carrying capacity for 2 core Amps

Current Carrying capacity for 3,4 core Amps

Voltage Drop for 2 core mV/A/m

Voltage Drop for 3,4 core mV/A/m

1.5

27

23

31

27

2.5

36

31

19

17

4

49

42

12

10

6

62

53

7.9

6.87

10

85

73

4.7

4.09

16

110

94

2.9

2.52

25

146

125

1.85

1.61

35

180

154

1.35

1.17

50

219

187

0.98

0.85

70

279

238

0.67

0.58

95

339

290

0.49

0.43

120

392

335

0.39

0.34

150

451

385

0.31

0.27

185

515

440

0.25

0.22

240

607

519

0.195

0.17

300

697

596

0.155

0.13

400

786

672

0.12

0.10

500

880

752

0.1

0.09

630

970

829

0.09

0.08