Application
The sheath is specially made out to resist tough and difficult outdoor conditions & excellent resistant to water
The PVC insulated and sheathed 3 core flat cables are mainly used in pump connections. They are also used in many industrial applications.
The sheath is specially made out to resist tough and difficult outdoor conditions & excellent resistant to water
Technical Data
Approvals : IS 694 marked, FIA/TAC
Conductor : Electrolytic grade annealed copper
Core Colour : Red, yellow (centre core), blue
Sheath Colour : Black
Voltage Grade : Upto and including 1100V
Packing : Standard packing of 100 mtr. in coils. Longer length available on request.
Variants Available
<
Product Type
|
Speci?cations
|
PVC 70°C
|
IS 694, IS 8130 Class 2 (1.5 & 2.5 Sq. mm), for others class 5, IS 5831 Type A insulation & ST-1 sheath.
|
HR 85°C
|
IS 694, IS 8130 Class 2 (1.5 & 2.5 Sq. mm), for others class 5, IS 5831 Type C insulation & ST-2 sheath.
|
Cable Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of 'y') for the cable type 1 – PVC 70°C, 3 - PVC HR 85°C.
Part Number
|
Conductor construction
|
Conductor resistance at 20 °C (Ω/km) Max.
|
Nom. Insulation thickness (mm)
|
Nominal Sheath Thickness (mm)
|
Approx. overall dimensions (W X H) (mm) +/- 0.5 mm
|
Current carrying capacity (Ampere)
|
Cross sectional area (Sq. mm)
|
No./Max. dia of strands (mm)
|
0118110102y1
|
0.5
|
16/0.2
|
39.0
|
0.6
|
0.9
|
9.60 X 4.90
|
4
|
0118110202y1
|
0.75
|
24/0.2
|
26.0
|
0.6
|
0.9
|
10.5 X 5.20
|
7
|
0118110302y1
|
1
|
32/0.2
|
19.5
|
0.6
|
0.9
|
11.0 X 5.40
|
12
|
0118110402y1
|
1.5*
|
22/0.3
|
12.1
|
0.6
|
0.9
|
12.0 X 5.6
|
18
|
0118110502y1
|
2.5*
|
36/0.3
|
7.41
|
0.7
|
1.0
|
13.0 X 6.2
|
24
|
0118110602y1
|
4
|
56/0.30
|
4.95
|
0.8
|
1.0
|
15.3 X 7.1
|
28
|
0118110702y1
|
6
|
84/0.30
|
3.30
|
0.8
|
1.1
|
19.2 X 8.4
|
36
|
0118110802y1
|
10
|
140/0.30
|
1.91
|
1.0
|
1.4
|
24.2 X 10.4
|
48
|
0118110902y1
|
16
|
126/0.40
|
1.21
|
1.0
|
1.4
|
29.0 X 12.4
|
64
|
0118111002y1
|
25
|
196/0.40
|
0.78
|
1.2
|
2.0
|
36.5 X 15.7
|
80
|
0118111102y1
|
35
|
276/0.40
|
0.554
|
1.2
|
2.0
|
40.5 X 17.2
|
100
|
0118111202y1
|
50
|
396/0.40
|
0.386
|
1.4
|
2.2
|
46.5 X 19.3
|
130
|
0118111302y1
|
70
|
360/0.50
|
0.272
|
1.4
|
2.2
|
52.0 X 21.0
|
192
|
0118111402y1
|
95
|
480/0.50
|
0.206
|
1.6
|
2.4
|
61.0 X 24.5
|
230
|
*Conductor configuration offered for 1.5 Sq mm-22/0.3 mm, 2.5 Sq mm - 36/0.3 mm (max.), class 2 as per IS 8130
Current rating conversion factor for deviating ambient temperature
Multiply the current carrying capacity of the cable by the factors given below for various ambient temperature.
Ambient Temperature (°C)
|
Derating Factor
|
25
|
1.25
|
30
|
1.16
|
35
|
1.09
|
40
|
1.00
|
45
|
0.90
|
50
|
0.81
|
55
|
0.74
|
60
|
0.68
|