Multicore Flexible Cable - H05VV-F

Multicore Flexible Cable - H05VV-F

Application


For use in connections of household appliances, plant and machinery, wiring purposes and for manufacturing cords.

Standard


BS EN 50525-2-11, DIN EN 50525-2-11; VDE 0285-525-2-11, EN 50525-2-11.

Technical Data


Nominal Voltage : 300/500V (H05VV-F & H05VVH2-F); 300/300V (H03VV-F & H03VVH2-F)
Insulation Resistance : Min. 20 GΩ x cm
Temperature Range : Flexing -5°C to +70°C. Fixed Installation : -30°C to +70°C Minimum Bending Radius: Flexing 7.5 x cable ø; Fixed installation 4 x cable ø Test Voltage : 4000V
Breakdown Voltage : Min. 8000V

Cable Construction


Bare copper, fine wire conductors, as per EN 60228 Cl.5. PVC core insulation TI2, to EN 50363-3.
Harmonised core colour to HD 308 (Refer Appendix Table No. 1-1). Cores stranded in layers with optimal lay-length.
PVC outer sheath TM2, to EN 50363-4.1.
The outer sheath provided here is of special PVC, TM5 to BS EN 50363-4.1.
H05VV-F is also available in oil resistant variant as H05VV5-F.

Properties


PVC self-extinguishing and flame retardant according to EN 60332-1-2.

Please complete the part numbers for these cables by adding the suffix (in place of 'z') for the sheath colour required:

- black (RAL 9005), 3 - grey (RAL 7001), 5 - white (RAL 9010). For Oil Resistant sheath kindly add 'OR' after the part nos.

Cable Design Parameters

 

 

 

Part Number

NO. OF CORES AND NOMINAL CROSS SECTIONAL AREA (SQ. MM)

APPROX. CABLE DIAMETER (MM)

H03VV-F

03030101021z

2 x 0.5

5.1

03030102021z

2 x 0.75

5.5

03030103021z

3 x 0.5

5.3

03030104011z

3 G 0.5

5.3

03030105021z

3 x 0.75

5.7

03030106011z

3 G 0.75

5.7

03030107021z

4 x 0.5

5.8

 

 

Part Number

 

03030108011z

No. of Cores and Nominal Cross Sectional Area (Sq. mm)

 

4 G 0.5

Approx. Cable Diameter (mm)

 

5.8

 

03030109021z

4 x 0.75

6.3

03030110011z

4 G 0.75

6.3

 

H03VVH2-F

03031111021z

2 x 0.5

5.1 x 3.2

03031112021z

2 x 0.75

5.5 x 3.4

 

H05VVH2-F

03031113021z

2 x 0.75

6.3 x 4.0

03031114021z

2 x 1

6.6 x 4.1

03031115021z

2 x 1.5

7.7 x 4.7

 

H05VV-F

03030116021z

2 x 0.75

6.2

03030117021z

2 x 1

6.4

03030118021z

2 x 1.5

7.5

03030119021z

2 x 2.5

9.1

03030120021z

2 x 4

10.3

03030121011z

3 G 0.75

6.6

03030122021z

3 x 0.75

6.6

03030123011z

3 G 1

6.9

03030124021z

3 x 1

6.9

03030125011z

3 G 1.5

8.1

03030126021z

3 x 1.5

8.1

03030127011z

3 G 2.5

9.7

03030128021z

3 x 2.5

9.7

03030129011z

3 G 4

11.2

03030130021z

3 x 4

11.2

03030131011z

4 G 0.75

7.1

03030132021z

4 x 0.75

7.1

03030133011z

4 G 1

7.5

03030134021z

4 x 1

7.5

03030135011z

4 G 1.5

9.1

03030136021z

4 x 1.5

9.1

03030137011z

4 G 2.5

10.7

03030138021z

4 x 2.5

10.7

03030139011z

4 G 4

12.2

03030140021z

4 x 4

12.2

03030141011z

5 G 0.75

8.0

03030142021z

5 x 0.75

8.0

03030143011z

5 G 1

8.4

03030144021z

5 x 1

8.4

 

 

Part Number

 

03030145011z

No. of Cores and Nominal Cross Sectional Area (Sq. mm)

 

5 G 1.5

Approx. Cable Diameter (mm)

 

10.2

 

03030146021z

5 x 1.5

10.2

03030147011z

5 G 2.5

12.0

03030148021z

5 x 2.5

12.0

03030149011z

5 G 4

13.8

03030150021z

5 x 4

13.8

Note :

*G = With green/yellow earth core

x = Without green/yellow earth core

Range Details

 

 

BASEC

VDE

H03VVH2-F

-

0.50…0.75 mm² x 2C

H05VVH2-F

0.75 1.5 mm² x 2C

0.75…1 mm² x 2C

H05VV-F

0.75…4 mm² x 2…5C

0.75…4 mm² x 2…3C

For current rating refer table no. 5-1 & for voltage drop refer table no. 5-2 of Appendix For current rating conversation factor, refer table no. 5-3 of Appendix