Double Insulated PVC Wires (6181Y)

Double Insulated PVC Wires (6181Y)

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 6004:2012, EN 50363-3 with BS 7655-4.2 (Only for sheath).

Technical Data

Voltage Rating : 1.5 mm2 to 35 mm2 - 300 / 500V Temperature Range : -15°C to 70 °C Minimum Bending Radius
Upto 10 mm2 : 10 X Overall Diameter. 16 & 35 mm2 : 12 X Overall Diameter.
16 & 35 mm2 : 12 X Overall Diameter.
Test Voltage : 2 kV for 15 min

Cable Construction

Conductor :

Plain annealed copper conductor : 1.5 & 2.5 mm2 Class -1, 4.0 to 35 mm2 stranded Class 2 complying with BS EN 60228, HD 383, IEC 60228.
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3 Sheath : PVC (Polyvinyl Chloride ) compound type Type 6 complying with BS 7655-4.2 Insulation Colours : Blue and brown
Sheath Colour : Grey RAL 7001

 

Cable Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of 'xx') for the colour required: 04 - blue, 09 - brown

 

Nominal Cross

Nominal

Nominal Sheath

Overall Diameter

Overall Diameter Approx. Net

Part Number

Sectional Area

(Sq. mm)

Insulation

Thickness (mm)

Thickness

(mm)

Lower Limit

(mm)

Upper Limit

(mm)

Weight (kg/km)

01150101xx10

1.5

0.70

0.8

4.20

5.00

37

01150102xx10

2.5

0.80

0.8

4.80

5.70

51

01150103xx10

4

0.80

0.9

5.50

6.70

75

01150104xx10

6

0.80

0.9

6.00

7.30

98

01150105xx10

10

1.00

0.9

7.30

8.80

152

01150106xx10

16

1.00

1.0

8.40

10.10

220

01150107xx10

25

1.20

1.1

10.00

12.10

336

01150108xx10

35

1.20

1.1

11.10

13.50

353