LOADING...

MYANMAR
3:42 AM

Single Core Fire Resistant Cables

Single Core Fire Resistant Cables

Application

These cables are designed for installations in trunking and conduits where a fire situation may pose a major hazard. Circuit integrity is maintained and to achieve optimum performance such cables should be installed in metal conduits.

General Characteristics

Temperature Rating : -20°C  to  +90°C
Minimum Bending Radius Fixed : 8 x overall diameter
Voltage    Rating    (Uo/U)    :    450/750V
Sheath color : Generally Black

Cable Construction

Conductors : Stranded plain annealed copper conductor to BS EN 60228, class 2.

Insulation : Mica (fire resistant) tape covered by an extruded layer of cross - linked low smoke zero halogen (LS0H), insulating compound

 

Properties

Circuit Integrity for installation in metal conduits: BS 6387 categories C, W & Z (when applied to a single cable)

Exceeds IEC 60331 - 3 hours at 750°C - when the test temperature was increased to 950°C, equivalent to BS 6387 category C

Acid Gas Emission : IEC 60754-1, BS EN 50267-2-1

Smoke Emission : IEC 61034, BS EN 50268

Flame Propagation : EN 60332-1, EN 60332-3, BS EN 50265, BS EN 50266

Cable Technical Data

Nominal area Sq.mm

Insulation thickness mm

Max. Overall diameter mm

Maximum current rating Amps

Voltage drop Mv/A/m

1.5

0.7

3.8

21

23

2.5

0.8

4.5

30

31

4

0.8

5

41

40

6

0.8

5.5

53

54

10

1

7

75

75

16

1

8

100

100

25

1.2

9.7

136

133

35

1.2

10.8

167

164

50

1.4

13.3

198

195

70

1.4

15.1

253

253

95

1.6

17.5

306

306

120

1.6

19.2

359

354

150

1.8

21.2

393

393

185

2

23.6

449

449