Building Wire - 6181XY - BS 7889 | Electrical Power Cable | RR Global UK

6181XY - BS 7889

RR Kabel

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded
conduits and in closed installation ducts. Ideal for internal wiring of appliance.

Standard

BS 7889.

Technical Data

Voltage Rating : 1.5 mmsquare to 630 mmsquare - 600 / 1000V
Temperature Range : -15 °C to 90°C
Minimum Bending Radius
4.0 to 50 mmsquare : 10 X Overall diameter.
70 & 630 mmsquare : 12 X Overall diameter.
Test Voltage : 2 kV 15 min.

Cable Construction

Conductor
Plain annealed copper conductor : 4 mmsquare to 630 mmsquare stranded class 2 complying with BS EN 60228, HD 383, IEC 60228
Insulation : GP8 conforming to BS 7655-1.3 ( XLPE )
Sheath : Type 9 specified in BS 7655-4.2
Insulation Colour : Natural
Sheath Colour : Black

Cable Design Parameters

Part Number Nominal Cross Sectional Area (Sq. mm) Nominal Insulation Thickness (mm) Nominal Sheath Thickness (mm) Approx Overall Diameter (mm) Approx. Net Weight (kg/km)
011600100004 4 0.70 1.40 8.0 107
011600100006 6 0.70 1.40 8.5 132
011600100010 10 0.70 1.40 9.5 181
0116001000160 16 0.70 1.40 10.5 247
011600100025 25 0.90 1.40 12.0 358
011600100035 35 0.90 1.40 13.0 466
011600100050 50 1.00 1.40 14.0 545
011600100070 70 1.10 1.40 16.0 765
011600100095 95 1.10 1.50 18.0 1022
011600100120 120 1.20 1.50 20.0 1267
011600100150 150 1.40 1.60 22.0 1556
011600100185 185 1.60 1.60 24.0 1928
011600100240 240 1.70 1.70 27.0 2501
011600100300 300 1.80 1.80 29.0 3108
011600100400 400 2.00 1.90 32.0 3923
011600100500 500 2.20 2.00 36.0 4999
011600100630 630 2.40 2.20 40.0 6414
GET IN TOUCH

Contact Us